เครื่องวัดและควบคุมก๊าซคาร์บอนไดออกไซด์ AMT72
Wall Mount CO2, Temperature, RH Monitor & Controller
Features:
- Dual Beam NDIR (Non-Dispersive-Infrared) technology used to measure CO2 concentration.
- Three different LED display show the current Indoor Air Quality situation. (HVAC/Green House Mode)
- Linear analog output (0~10V Voltage, 4~20mA Current) and Relay output based on CO2 Level.
- Reliable Sensor provides long-term calibration stability.
- The visual and audible alarm function can be adjustable by user.
- Mounting bracket with terminal block provides quick easy installation.
Specifications – CO2:
Measurement Range |
0~3,000ppm display
|
Display Resolution |
1ppm at 0~1,000ppm; 10ppm at 1,001~3,000ppm |
Accuracy |
±75ppm or ±5% of reading whichever is greater |
Repeatability |
±20ppm @400ppm |
Temperature Dependence |
Typ. ±0.2% of reading per °C or ±2ppm per °C, whichever is greater, referenced to 25°C |
Pressure Dependence |
0.13% of reading per mm Hg |
Response Time |
About 2min for 90% of step change |
Warm-Up Time |
About 60 seconds at 22°C |
Sound Alarm |
About 65db@10cm> |
Zone LED Display |
Green:=1200ppm (HVAC mode) |
Green:>1000ppm Yellow:600~1000ppm Red: <=600ppm (Green House mode) | |
Power Supply |
18~26VAC RMS 50/60Hz or 18~36VDC (half-wave rectified, polarity protected) |
Linear Voltage Output |
0~10VDC (100 Ohms output impedance) |
Linear Current Output |
4~20mA (Max Load is 500 Ohm, Max Load is 400 Ohm while power supply< 20VDC ) |
Relay Output |
30VDC or 250VAC, max 2A ., SPST .Normally Open |
Operating Temperature |
0°C ~50°C (32°F~122°F) |
Operating Humidity Range |
0 ~ 95% RH non-condensing |
Storage Temperature |
-20°C to +60°C (-4°F to 140°F) |
Specifications – Temperature
Temperature Range |
Display 0°C to 50°C
|
Display Resolution |
0.1°C |
Display Options |
°C |
Accuracy (Relay no action and be under the alarm level) |
±1°C; when the fan blows to the device directly, the accuracy of temperature is +/-1.5°C |
Accuracy (Relay action and exceeds the alarm level) |
±2.5°C; when the fan blows to the device directly, the accuracy of temperature is +/-1.5°C |
Response Time |
20-30 minutes (case must equalize with environment) |
Specifications – RH
Measurement Range |
20%-90% RH
|
Display Resolution |
1%RH |
Accuracy | ±5%RH@ 23°C |
Response Time | About 5 min for 63% of step change |